DPR Feb. 15, 2006, No. 147

Regulation 2037/2000/EC - Arrangements for the control and recovery of leakage of ozone depleting substances layer from refrigeration and air conditioning and heat pumps.



Article 1.
Aims and Scope

1. This Regulation regulates the technical standards and procedures for the prevention, reduction and recovery of emissions of controlled substances from certain facilities and equipment containing them.

2. This Regulation applies to facilities and equipment, air conditioning and heat pumps in the circuit containing controlled substances.


Article 2.


Definition 1. For the sole purpose of this Regulation the following definitions:
a) Controlled substances, the ozone layer depleting substances referred to in subparagraphs b) and c);
b) "CFC" means substances listed in Group I and II of Annex I to Regulation (EC) No 2037/2000;
c) "HCFCs" means any substance listed in Group VIII of Annex I to Regulation (EC) No 2037/2000;
d) "Recovery" means the collection and storage of controlled substances from, for example, machinery, equipment, containment vessels during servicing or before disposal,
e) "recycling "the reuse of ozone depleting substances recovered following a basic cleaning process such as filtering and drying. For refrigerants, recycling normally involves recharge back into equipment often carried out on site;
f) "reclamation" means reprocessing and upgrading of a recovered controlled substance through such processes as filtering, drying, distillation and chemical treatment in order to restore the substance to a specified standard of performance;
g) "destruction" permanent transformation or decomposition of all or a significant portion of the controlled substance by a technology approved by the Parties to the Montreal Protocol on substances harmful to the ozone layer;
h) "maintenance" means repairs, replacement of refrigerant, including recovery, recycling and recharging, and periodic monitoring of equipment and refrigeration, air conditioning and heat pump equipment containing controlled substances ;
i) "operator" means any person or entity which owns or operates the plant or equipment in the circuit containing controlled substances.


Article 3.
recovery and recycling activities

1. The recovery and recycling of controlled substances contained in the cooling plant and refrigeration equipment, air conditioning and heat pumps are made with devices that conform to the characteristics and in compliance with technical standards established by ISO 11650.

2. The operator must keep a book of plant according to the model in Annex I. In the operating system must be recorded the transactions referred to in paragraph 1.

3. The devices referred to in paragraph 1 must comply with ISO 11650 within nine months from the date of entry into force of this Regulation.


Article 4. Leak checks


1. The equipment and refrigeration, air conditioning and heat pump equipment containing controlled substances in high quality 3 kg must be inspected for leakage in the refrigeration cycle, the frequency indicated in paragraph 2, of the register in the operating system listed in Annex I. Facilities and equipment in question must be checked with the following cadences:
a) annual, plant and equipment with a controlled substance content of between 3 and 100 kg;
b) half-year: for plant and equipment with a content of controlled substances in excess of 100 kg.

2. When in the course of an inspection is identified, an indication of the run, you must precede the leak detection device with a detector sensitivity of greater than 5 g / year. Research on the high side should be performed with the system running while the low side pressure should be performed with the system off.

3. When there is a loss that requires a recharge of more than 10 percent of the total content of the refrigerant circuit, the plant or equipment must be repaired within thirty days of the verification and can be operated only after the loss has been repaired.

4. The results must be recorded in the operating system referred to in Article 3, paragraph 2.





Article 5.


a minimum qualification requirements. The personnel carrying out activities referred to in Articles 1, 3 and 4 must be in possession of the minimum requirements established within the Permanent Conference for Relations between State, Regions and Autonomous Provinces of Trento and Bolzano, in accordance with Article 4 of Legislative Decree August 28, 1997, No 281.


Article 6. Final provision


1. The implementation of this Regulation should not derive new or increased burdens on public finances.

This decree, bearing the seal of the State, will be included in the official collection of normative acts of the Italian Republic. E 'is mandatory for all to observe and enforce them.